INSTRUCTION MANUAL FOR BE1-11 Protection Systems IEC 61850 Protocol Publication: 9424200892 Revision: F Sep-14
4 9424200892 Rev F General Information BE1-11
12570 State Route 143 Highland IL 62249-1074 USA Tel: +1 618.654.2341 Fax: +1 618.654.2351 email: [email protected] P.A.E. Les Pins 67319 Wasselonne
9424200892 Rev F 5 IEC 61850 Engineering The engineering process and configuration of a substation is described in IEC 61850-Part 6: Configuration de
6 9424200892 Rev F IED Configurator Tool (BEST61850™) BEST61850 performs the following functions: • Imports an SCD file and extracts the necessary
9424200892 Rev F 7 Figure 4. Configuration Example (from IEC 61850-6) The IEC 61850 standard is based on the hierarchical addressing and information
8 9424200892 Rev F Figure 5. Modeling Approach Example Substation Configuration Description Language (SCL) The SCL language is based on XML (Exten
9424200892 Rev F 9 Figure 6. Principle Structure of the SCL XML File HeaderidtoolIDnameStructureHeaderSubstationVoltage LevelBayLNodeStationIEDIE
10 9424200892 Rev F Signal Identification Elements of the signal identification as defined in IEC 61850–7–2 are illustrated in Figure 7. Figure 7.
9424200892 Rev F 11 Figure 8. Elements of the Signal Name Using Product Naming Figure 9 shows an example of an IED (SB1) with logical devices LD1 an
12 9424200892 Rev F • the access points per IED to the sub networks • the address • the IP address of the LAN network is an exception also part
9424200892 Rev F 13 Figure 11. Organization of LDs, LNs, DOs, and DAs in an IED An IED server represents the communication interface to the sub netw
14 9424200892 Rev F Signal Engineering Signal engineering consists of DataSets, Report Control Blocks (RCB), and Goose Control Blocks (GoCB). DataS
9424200892 Rev F 15 also referred to as Data Tags. As specified in IEC 61850–7–2 clause 9, the DataSets are part of a Logical Node. They are included
16 9424200892 Rev F To send GOOSE messages, a GoCB must be defined and a DataSet is needed which contains the data objects of single data attribute
9424200892 Rev F 17 BESTCOMSPlus® BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user interface (GUI) for
18 9424200892 Rev F Figure 16. IEC61850PTRC Logic Block BESTCOMSPlus® BE1-11
9424200892 Rev F 19 BEST61850™ BEST61850 is a Windows®-based, PC application that provides a user-friendly, graphical user interface (GUI) for use wi
20 9424200892 Rev F 1. Insert the BEST61850 CD-ROM into the PC CD-ROM drive. 2. When the BEST61850 Setup and Documentation CD menu appears, click
9424200892 Rev F 21 Figure 17. Device Info Tab Device Info Settings The Device Info settings are described in Table 4. Table 4. Device Info Settings
22 9424200892 Rev F Figure 18. Datasets Tab Functional Constraints The IEC 61850 standard defines a number of functional constraints that indicate
9424200892 Rev F 23 Table 5. Datasets Settings Setting Range LDevice Inst List selectable Logical Node List selectable FC List selectable DO Name
9424200892 Rev F i Preface This instruction manual provides detailed information about BE1-11 Protection Systems with the IEC 61850 Protocol. To acco
24 9424200892 Rev F Setting Range GoID String (65) MAC Address 00 to FF (per each hexadecimal group) VLAN ID 000 to FFF VLAN Priority 0 to 7 M
9424200892 Rev F 25 Setting Range Dataset List selectable Data Tags List selectable Mapped To IED Name List selectable LDevice Inst List selecta
26 9424200892 Rev F The class BRCB allows for the sending of reports to be issued immediately, or for the events to be buffered for transmission af
9424200892 Rev F 27 Table 8. Report Controls Settings Setting Range Report ID n/a Name String (65) Configuration Revision 1 to 65535 DataSet Str
28 9424200892 Rev F Configuration Example This configuration example provides step-by-step instructions on how to configure two separate CIDs. Conf
9424200892 Rev F 29 Figure 25. BE1-11 BEST61850 Template Selection Screen Figure 26. Adding a Second SCL Template to the Workspace Configure DataSe
30 9424200892 Rev F Step 6: Right-click on the BE1_11_1 file in the Workspace and select Validate. The round indicator located on the left side of
9424200892 Rev F 31 Configure Published IED GOOSE Step 1: Select the Published IED GOOSE tab in BEST61850. See Figure 29. A maximum of four Publishe
32 9424200892 Rev F Table 9. Published IED GOOSE Example Values Setting Range Value GOOSE Control Name String (65) GCB1 Dataset String (255)
9424200892 Rev F 33 Figure 31. Subscribed IED GOOSE Tab Figure 32. Add New Subscribed GOOSE Screen Configure Report Control Blocks Step 1: Select
ii 9424200892 Rev F 12570 State Route 143 Highland IL 62249-1074 USA www.basler.com [email protected] Tel: +1 618.654.2341 Fax: +1 618.654.2351
34 9424200892 Rev F Figure 33. Report Controls Tab Figure 34. Add New Report Control Screen Step 4: Make the appropriate settings as shown in Ta
9424200892 Rev F 35 Table 10. Report Controls Settings Example Values Setting Range Value Report ID n/a BE1_11_1PRO/LLNO$bcrb1 Name String (65)
36 9424200892 Rev F Save a CID File as a User Template Using the mouse, left-click on and hold the BE1_11_1 file in the Workspace. While holding do
9424200892 Rev F 37 Save a CID File Right-click on the BE1_11_1 file in the Workspace and select Save CID. See Figure 36. Figure 36. Save a CID File
38 9424200892 Rev F Upload a CID File to the BE1-11 Right-click on the BE1_11_1 file in the Workspace and select Upload. See Figure 37. Figure 37.
9424200892 Rev F 39 The ctlModel enumeration lists a control type for values listed in Table 11. Table 11. ctlModel Symbols Value Definition 0 status
40 9424200892 Rev F Value Quantity Unit name Symbol 47 Moment of mass kilogram meter (kg m) M 48 Density kilogram/cubic meter (kg/m3) kg/m3 49 Visc
9424200892 Rev F 41 The deadband settings represent the deadband values used to determine when the measurement logic nodes “mag” and “cVal” values up
42 9424200892 Rev F Figure 41. MMXUN and MSQI Measurement Node Default Deadband Values Table 14. Summary of BE1-11 IEC 61850 Parameter Limits Par
9424200892 Rev F 43 File Transfer The BE1-11 can transmit the files listed in Table 15 when requested by a supported IEC 61850 client. Table 15. File
9424200892 Rev F iii Contents General Information ...
44 9424200892 Rev F File Transfer BE1-11
9424200892 Rev F 45 Data Tags The description of the DataSets and the list of data object members or FCDAs (Functionally Constrained Data Attributes)
44 9424200892 Rev F Data Tags CTLGGIO1.ST.SPCSO15.stVal CTLGGIO1.ST.SPCSO15.t CTLGGIO1.ST.SPCSO16.q CTLGGIO1.ST.SPCSO16.stVal CTLGGIO1.ST.SPCSO16.t
9424200892 Rev F 45 Data Tags CTLGGIO2.ST.SPCSO11.q CTLGGIO2.ST.SPCSO11.stVal CTLGGIO2.ST.SPCSO11.t CTLGGIO2.ST.SPCSO12.q CTLGGIO2.ST.SPCSO12.stVal C
46 9424200892 Rev F Data Tags CTLGGIO3.ST.Beh.t CTLGGIO3.ST.Health.q CTLGGIO3.ST.Health.stVal CTLGGIO3.ST.Health.t CTLGGIO3.ST.Mod.q CTLGGIO3.ST.Mo
9424200892 Rev F 47 Data Tags CTLGGIO4.DC.SPCSO14.d CTLGGIO4.DC.SPCSO15.d CTLGGIO4.DC.SPCSO16.d CTLGGIO4.DC.SPCSO2.d CTLGGIO4.DC.SPCSO3.d CTLGGIO4.DC
48 9424200892 Rev F Data Tags IABCMMXU1.ST.Health.q IABCMMXU1.ST.Health.stVal IABCMMXU1.ST.Health.t IABCMMXU1.ST.Mod.q IABCMMXU1.ST.Mod.stVal IABCM
9424200892 Rev F 49 Data Tags INDGGIO1.ST.Health.stVal INDGGIO1.ST.Health.t INDGGIO1.ST.Ind01.q INDGGIO1.ST.Ind01.stVal INDGGIO1.ST.Ind01.t INDGGIO1.
50 9424200892 Rev F Data Tags INDGGIO2.ST.Ind06.t INDGGIO2.ST.Ind07.q INDGGIO2.ST.Ind07.stVal INDGGIO2.ST.Ind07.t INDGGIO2.ST.Ind08.q INDGGIO2.ST.I
9424200892 Rev F 51 Data Tags INDGGIO3.ST.Ind13.q INDGGIO3.ST.Ind13.stVal INDGGIO3.ST.Ind13.t INDGGIO3.ST.Ind14.q INDGGIO3.ST.Ind14.stVal INDGGIO3.ST
iv 9424200892 Rev F TICS...
52 9424200892 Rev F Data Tags LLN0.SP.SGCB.EditSG LLN0.SP.SGCB.LActTm LLN0.SP.SGCB.NumOfSG LLN0.ST.Beh.q LLN0.ST.Beh.stVal LLN0.ST.Beh.t LLN0.ST.He
9424200892 Rev F 53 Data Tags MMXU1.CF.W.phsB.db MMXU1.CF.W.phsB.units.multiplier MMXU1.CF.W.phsB.units.SIUnit MMXU1.CF.W.phsC.db MMXU1.CF.W.phsC.uni
54 9424200892 Rev F Data Tags MMXU1.MX.W.phsB.t MMXU1.MX.W.phsC.cVal.mag.f MMXU1.MX.W.phsC.q MMXU1.MX.W.phsC.t MMXU1.ST.Beh.q MMXU1.ST.Beh.stVal MM
9424200892 Rev F 55 Data Tags MSQI2.ST.Beh.t MSQI2.ST.Health.q MSQI2.ST.Health.stVal MSQI2.ST.Health.t MSQI2.ST.Mod.q MSQI2.ST.Mod.stVal MSQI2.ST.Mod
56 9424200892 Rev F Data Tags P49RTDPTTR1.ST.Op.t P49RTDPTTR1.ST.Str.dirGeneral P49RTDPTTR1.ST.Str.general P49RTDPTTR1.ST.Str.q P49RTDPTTR1.ST.Str.
9424200892 Rev F 57 Data Tags P49RTDPTTR14.ST.Str.t P49RTDPTTR2.CF.Mod.ctlModel P49RTDPTTR2.DC.NamPlt.d P49RTDPTTR2.ST.Beh.q P49RTDPTTR2.ST.Beh.stVal
58 9424200892 Rev F Data Tags P49RTDPTTR7.ST.Beh.stVal P49RTDPTTR7.ST.Beh.t P49RTDPTTR7.ST.Health.q P49RTDPTTR7.ST.Health.stVal P49RTDPTTR7.ST.Heal
9424200892 Rev F 59 Data Tags P78PPAM1.ST.Beh.t P78PPAM1.ST.Health.q P78PPAM1.ST.Health.stVal P78PPAM1.ST.Health.t P78PPAM1.ST.Mod.q P78PPAM1.ST.Mod.
60 9424200892 Rev F Data Tags PDIS1.ST.Mod.q PDIS1.ST.Mod.stVal PDIS1.ST.Mod.t PDIS1.ST.Op.general PDIS1.ST.Op.q PDIS1.ST.Op.t PDIS1.ST.Str.dirGene
9424200892 Rev F 61 Data Tags PFRC1.ST.Op.q PFRC1.ST.Op.t PFRC1.ST.Str.dirGeneral PFRC1.ST.Str.general PFRC1.ST.Str.q PFRC1.ST.Str.t PFRC2.CF.Mod.ctl
9424200892 Rev F 1 General Information This document describes the Basler Electric IEC 61850 Protocol implementation in the BE1-11 series of protecti
62 9424200892 Rev F Data Tags PIOC4.ST.Str.q PIOC4.ST.Str.t PIOC5.CF.Mod.ctlModel PIOC5.DC.NamPlt.d PIOC5.ST.Beh.q PIOC5.ST.Beh.stVal PIOC5.ST.Beh.
9424200892 Rev F 63 Data Tags PMRI1.ST.Beh.q PMRI1.ST.Beh.stVal PMRI1.ST.Beh.t PMRI1.ST.Health.q PMRI1.ST.Health.stVal PMRI1.ST.Health.t PMRI1.ST.Mod
64 9424200892 Rev F Data Tags PTOC4.ST.Str.dirGeneral PTOC4.ST.Str.general PTOC4.ST.Str.q PTOC4.ST.Str.t PTOC5.CF.Mod.ctlModel PTOC5.DC.NamPlt.d PT
9424200892 Rev F 65 Data Tags PTOF1.CF.Mod.ctlModel PTOF1.DC.NamPlt.d PTOF1.ST.Beh.q PTOF1.ST.Beh.stVal PTOF1.ST.Beh.t PTOF1.ST.Health.q PTOF1.ST.Hea
66 9424200892 Rev F Data Tags PTOV2.ST.Beh.t PTOV2.ST.Health.q PTOV2.ST.Health.stVal PTOV2.ST.Health.t PTOV2.ST.Mod.q PTOV2.ST.Mod.stVal PTOV2.ST.M
9424200892 Rev F 67 Data Tags PTOV7.ST.Mod.q PTOV7.ST.Mod.stVal PTOV7.ST.Mod.t PTOV7.ST.Op.general PTOV7.ST.Op.q PTOV7.ST.Op.t PTOV7.ST.Str.dirGenera
68 9424200892 Rev F Data Tags PTUF2.ST.Health.t PTUF2.ST.Mod.q PTUF2.ST.Mod.stVal PTUF2.ST.Mod.t PTUF2.ST.Op.general PTUF2.ST.Op.q PTUF2.ST.Op.t PT
9424200892 Rev F 69 Data Tags PTUV3.ST.Op.general PTUV3.ST.Op.q PTUV3.ST.Op.t PTUV3.ST.Str.dirGeneral PTUV3.ST.Str.general PTUV3.ST.Str.q PTUV3.ST.St
70 9424200892 Rev F Data Tags PTUV8.ST.Str.general PTUV8.ST.Str.q PTUV8.ST.Str.t PTUV9.CF.Mod.ctlModel PTUV9.DC.NamPlt.d PTUV9.ST.Beh.q PTUV9.ST.Be
9424200892 Rev F 71 Data Tags RBRF1.DC.NamPlt.d RBRF1.ST.Beh.q RBRF1.ST.Beh.stVal RBRF1.ST.Beh.t RBRF1.ST.Health.q RBRF1.ST.Health.stVal RBRF1.ST.Hea
2 9424200892 Rev F The BE1-11 is capable of transmitting the following items on an IEC 61850 network: • Configuration Settings • Metering • Stat
72 9424200892 Rev F Data Tags RSYN1.ST.VInd.stVal RSYN1.ST.VInd.t VXMMXN1.CF.Mod.ctlModel VXMMXN1.CF.Vol.db VXMMXN1.CF.Vol.units.multiplier VXMMXN1
9424200892 Rev F 73 Conformance Statements The following conformance statements described in this chapter are applicable for a BE1-11 Protection Syst
74 9424200892 Rev F BE1-11f BE1-11i BE1-11g BE1-11t BE1-11m Overvoltage : PTOV1, PTOV2, PTOV3, PTOV4 59P-1 to 4 59P-1 to 4 59P-1 to 4 59P-1 to
9424200892 Rev F 75 BE1-11f BE1-11i BE1-11g BE1-11t BE1-11m Z: Other Motor: ZMOT Output Logic Point PICS The following ACSI conformance statemen
76 9424200892 Rev F Table 20. ACSI Models Conformance Statement Client/subscriber Server/publisher Value/comments IF SERVER SIDE (B11) SUPPORTED M
9424200892 Rev F 77 Client/subscriber Server/publisher Value/comments IF SVC (B41/B42) IS SUPPORTED M14 Multicast SVC O O No M15 Unicast SVC O O No
78 9424200892 Rev F SERVICES AA: TP/MC Client/ subscriber Server/ publisher Value/ comments SETTING GROUP CONTROL S18 SelectActiveSG TP O O Yes S1
9424200892 Rev F 79 SERVICES AA: TP/MC Client/ subscriber Server/ publisher Value/ comments GSSE-CONTROL-BLOCK S40 SendGSSEMessage MC c8 c8 No S41
80 9424200892 Rev F SERVICES AA: TP/MC Client/ subscriber Server/ publisher Value/ comments Notes: c6 - shall declare support for at least one (BR
9424200892 Rev F 81 Table 23. PIXIT for Server Model Description Value / Clarification Which analogue value (MX) quality bits are supported (can be s
9424200892 Rev F 3 BEST61850™ BEST61850 software is provided with the BE1-11. Refer to the BEST61850 chapter for more information. BEST61850 performs
82 9424200892 Rev F Table 24. PIXIT for Data Set Model Description Value / Clarification What is the maximum number of data elements in one data s
9424200892 Rev F 83 Description Value / Clarification Pre-configured RCB attributes that cannot be changed online when RptEna = FALSE (see also the I
84 9424200892 Rev F Description Value / Clarification What is the fast retransmission scheme? Is it fixed or configurable? 1) 4 msec with TAL = 8
9424200892 Rev F 85 Description Value / Clarification How to force a “test-not-ok” respond with Select request? n/a How to force a “test-not-ok” resp
86 9424200892 Rev F Table 30. PIXIT for File Transfer Model Description Value / Clarification What is structure of files and directories? comtrade
9424200892 Rev F 87 Part Tissue Description Nr Implemented Y/n/a 7-2 30 control parameter T Y 31 Typo n/a 32 Typo in syntax n/a 35 Typo Syntax
88 9424200892 Rev F Part Tissue Nr Description Implemented Y/N/n/a 7-2 333 Enabling of an incomplete GoCB N 7-2 453 Combination of all reporting an
9424200892 Rev F 89 Revision History Table 33 provides a historical summary of the changes made to the BEST61850™ software. The corresponding revisio
90 9424200892 Rev F Revision History BE1-11