Basler-electric BE1-851 Modbus Protocol Bedienungsanleitung Seite 45

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 70
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 44
9289900992 Rev F BE1-851 Modbus Protocol 3-7
40135 Select 101 Virtual Breaker Control Switch ASC(1)
Read: To read a value other than ASCII character ‘X’, the Select 101 Virtual Breaker
Control Switch register must be the most recent control register written AND must have
been written within the previous 30 seconds.
C if Close selection has been made.
T if Trip selection has been made.
X if 101 Virtual Breaker Control Switch control not selected or control timer has
expired
Write: The desired ASCII character.
C to select Closing the Switch.
T to select Tripping the Switch.
40136 Operate 101 Virtual Breaker Control Switch ASC(1)
Read: Current control.
C if Close Switch.
T if Trip Switch.
Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).
C to Close Switch.
T to Trip Switch.
40137 Select All Outputs ASC(1)
Read: To read a value other than ASCII character ‘X’, the Select All Output register must
be the most recent control register written AND must have been written within the
previous 30 seconds.
P if Pulse All Outputs selection has been made.
0 if Latch All Outputs at 0 selection has been made.
1 if Latch All Outputs at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs override control has been set.
D if Disable All Outputs override control has been set.
X if All Outputs control not selected or control timer has expired.
Write: The desired ASCII character.
P to select Pulsing All Outputs.
0 to select Latching All Outputs at 0.
1 to select Latching All Outputs at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.
40138 Operate All Outputs ASC(1)
Read: Current control.
E if All Outputs override control Enabled.
D if All Outputs override control Disabled.
Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).
P to Pulse All Outputs.
0 to Latch All Outputs at 0.
1 to Latch All Outputs at 1.
L to select programmable Logic.
E to Enable All Outputs override control.
D to Disable All Outputs override control.
40139 Select Output A ASC(1)
40141 Select Output 1 ASC(1)
40143 Select Output 2 ASC(1)
40145 Select Output 3 ASC(1)
40147 Select Output 4 ASC(1)
40149 Select Output 5 ASC(1)
Seitenansicht 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 69 70

Kommentare zu diesen Handbüchern

Keine Kommentare