3-8 BE1-851 Modbus Protocol 9289900992 Rev F
Read: To read a value other than ASCII character ‘X’, the Select Output register must be
the most recent control register written AND must have been written within the previous
30 seconds.
P if Pulse Output selection has been made.
0 if Latch Output at 0 selection has been made.
1 if Latch Output at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs serial control has been made.
D if Disable All Outputs serial control has been made.
X if Output control not selected or control timer has expired
Write: The desired ASCII character.
P to select Pulsing Output.
0 to select Latching Output at 0.
1 to select Latching Output at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.
40140 Operate Output A ASC(1)
40142 Operate Output 1 ASC(1)
40144 Operate Output 2 ASC(1)
40146 Operate Output 3 ASC(1)
40148 Operate Output 4 ASC(1)
40150 Operate Output 5 ASC(1)
Read: Current control.
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
D if All Outputs override control Disabled
Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
E to Enable All Outputs override control.
D to Disable All Outputs override control.
Requires an additional write of ‘Y’ to Exit register 40001 to allow these control settings to be saved to
the relay’s internal EEPROM (if Modbus password security is enabled).
† 243 and 343 are not available when style option 1 is V or W.
Group Setting Parameters
40269-70 50TP Pickup FP
40273-74 50TN Pickup FP
40277-78 50TQ Pickup (250TN, Sensing input “G”) FP
40281-82 150TP Pickup FP
40285-86 150TN Pickup FP
40289-90 150TQ Pickup (350TN, Sensing input “G”) FP
Read and Write:
0.50 to 150.00 amps (5A units)
40271-72 50TP Time Delay LI
40275-76 50TN Time Delay LI
40279-80 50TQ Time Delay (250TN, Sensing input “G”) LI