9424200994 Rev N 101
Figure 65. Inverse Overcurrent Settings Screen
Table 36. Operational Settings
Setting Range Increment
Unit of
Measure
Default
Mode
Disabled, IA, IB, IC, 3 Phase,
3I0, I1, I2, IG, or Unbalance
n/a n/a Disabled
Source*
CT Circuit 1 or CT Circuit 2
n/a
n/a
CT Circuit 1
Pickup
0 or 0.5 to 16 (5A CTs)
0 or 0.1 to 3.2 (1A CTs)
0 or 0.01 to 0.8 (SEF)
varies amps
0
2 to 100 (Unbalance mode)
1
percent
Time Dial
0 to 9.9
0 to 1 (IEC curves only)
0.0 to 99 (46 only)
varies units 0
Curve
See the Time Curve
Characteristics chapter.
n/a n/a S1
Direction
Forward, Reverse, or Non-
Directional
n/a n/a
Non-
Directional
Reset Timing
Integrating or Instantaneous
n/a
n/a
Instantaneous
A Coefficient
0 to 600
0.00001
A Coefficient
0.26630
B Coefficient
0 to 25
0.00001
B Coefficient
0.03393
BE1-11g Inverse Overcurrent (51) Protection