9424200994 Rev N 485
2
nd
Harmonic Restraint Verification (Independent)
Pickup Accuracy = ±2% or ±0.05A, whichever is greater.
Step
Pickup Setting
Low
Actual Pickup
High
Pass/Fail
5
0.24 A
0.19 A
0.29 A
P / F
2
nd
Harmonic Restraint Verification (Shared)
Pickup Accuracy = ±2% or ±0.05A, whichever is greater.
Step
Pickup Setting
Low
Actual Pickup
High
Pass/Fail
5
3 x (0.08) A
3x (0.06) A
3 x (0.10) A
P / F
5
th
Harmonic Restraint Verification (Independent)
Pickup Accuracy = ±2% or ±0.05A, whichever is greater.
Step
Pickup Setting
Low
Actual Pickup
High
Pass/Fail
5
0.24 A
0.19 A
0.29 A
P / F
5
th
Harmonic Restraint Verification (Shared)
Pickup Accuracy = ±2% or ±0.05A, whichever is greater.
Step
Pickup Setting
Low
Actual Pickup
High
Pass/Fail
5
3 x (0.23) A
3x (0.22) A
3 x (0.25) A
P / F
BE1-11g Phase Current Differential (87) Test